Eaton Powerware 5130 2500/ 3000va Extended Battery Module Rack/ Tower 2u 72vdc

SKU
53428
Brand
Warranty
Standard Manufacturer's Warranty

No Longer Available

$192.00
Buy Now And Earn 192 Reward Points!

LEDs 13 status-indicating LEDs
Topology Line interactive
Diagnostics Full system self-test at power up
Transfer Time 1?4 ms typical
ROO/RPO Rear deck emergency stop connector (for remote on/off and power off)
Rail Kit/Tower Stand Included with all units
Electrical Input
Nominal Voltage 230 Vac
Voltage Range 160?294V
(* The high and low thresholds can be user adjusted using the downloadable UPS Configuration tool)
Frequency 50/60 Hz
Frequency Range 47?70 Hz for 50 Hz operation
56.5?70 Hz for 60 Hz operation
Power Draw of UPS (full load) 1250: 5.4A @230V
1750: 7.6A @230V
2500: 10.9A @230V
3000: 13.0A @230V
Electrical Output
Power Factor 0.9
On Utility Voltage Regulation 184?265 Vac
On Battery Voltage Regulation -10%, +6% of nominal
Efficiency Normal or line mode: >94%
Frequency Regulation 0.1 Hz
Over Current Protection Electronic current limit
Load Crest Factor 3:1
Load Segments Two individually controlled output receptacles
Battery
Internal Battery Type 1250/2500 VA: 12V/7.2 Ah; sealed, lead-acid; maintenance free
1750/3000 VA: 12V/9 Ah; sealed, lead-acid; maintenance free
EBM Battery Type 12V/9 Ah
Battery Runtime 1250 VA: 5 min w/internal batteries @100% load (0.9 PF)
1750 VA: 3.5 min w/internal batteries @100% load (0.9 PF)
2500?3000 VA: 3 min w/internal batteries @100% load (0.9 PF)
Battery Replacement Hot-swappable internal batteries
Start-On-Battery Allows start of UPS without utility input
Communications
Serial Port RS-232 (RJ45) ports
USB Port As standard (HID)
Optional Communications Slots ConnectUPS-MS network management card and ModBus
Cables RS-232 and USB 6-foot communications cables included
Power Management Software Powerware Software Suite CD-ROM (bundled with UPS)
Environmental
Safety Markings CE, cTUVus; C-Tick
Safety Conformance IEC/EN 62040-1-1,; UL 1778
EMC Compliance IEC 62040-2, class B
Operating Temperature 0˚C to +40˚C
Storage Temperature -15˚C to +50˚C
Relative Humidity 20?95% non-condensing
Surge Suppression ANSI C62.41 Category A (formerly IEEE 587)
Audible Noise Max 45 dBA
Heat Dissipation Table
Eaton 5130 Model Line Mode, BTUs/hr Battery Mode, BTUs/hr
1250 VA 250 1,682
1750 VA 348 2,340
2500 VA 490 2,559
3000 VA 588 3,071
(Battery fully charged)
Model Selection Guide
Catalog Number Rating (VA/Watts) Input connection Output Receptacles Dimensions
H x W x D, mm Weightkg
Rack/Tower Models
PW5130i1250-XL2U 1250/1150 IEC C14-10A (8) IEC-C13-10A 86.2 x 441 x 509 24.3
PW5130i1750-XL2U 1750/1600 IEC C14-10A (8) IEC-C13-10A 86.2 x 441 x 509 26.6
PW5130i2500-XL2U 2500/2250 IEC C20-16A (1) IEC-C19 16A, (8) IEC-C13 10A 86.2 x 441 x 634 33.8
PW5130i3000-XL2U 3000/2700 IEC C20-16A (1) IEC-C19 16A, (8) IEC-C13 10A 86.2 x 441 x 634 33.8
PW5130i3000-XL3U 3000/2700 IEC C20-16A (1) IEC-C19 16A, (8) IEC-C13 10A 130.7 x 441 x 484 34.3
Battery Backup Times (in minutes)
Load (VA/Watts) Internal
Batteries 1 EBM 2 EBMs 3 EBMs 4 EBMs
PW5130i1250-XL2U
125/115 119 430 741 1052 1363
313/288 32 150 267 384 502
625/575 15 58 100 143 185
938/863 6 42 77 113 148
1250/1150 5 29 54 79 104
PW5130i1750-XL2U
175/160 80 245 410 575 740
438/400 24 96 168 240 312
875/800 9 36 62 89 115
1313/1200 6 24 42 60 79
1750/1600 3 16 28 41 53
PW5130i2500-XL2U
250/225 77 300 410 780 1064
625/563 28 122 207 309 412
1250/1125 11 55 100 150 206
2153/1938 6 31 59 90 120
2500/2250 3 23 42 63 85
PW5130i3000-XL2U / XL3U
300/270 70 242 448 634 820
750/675 24 105 180 255 330
1500/1350 10 44 73 101 130
2250/2025 5 25 47 69 91
3000/2700 3 17 32 47 62

Maximizes availability with extended battery runtime options.Note: This is an Extended Battery Module (EBM) that must be connected to a 5130 UPS.