Delta Rt-Series Online 1Kva/ 0.9Kw Ups 2U Lcd Display 3 Years Advanced Replacement Warranty Australian
SKU
275588
Brand
Warranty
Standard Manufacturer's Warranty
No Longer Available
$894.00
Buy Now And Earn 894 Reward Points!
QUICK OVERVIEW
Input Cord Ups And Batteries Inclusive Ear Ups102R2Rt0B0Bb
Availability
True online double-conversion topology and zero transfer time to battery ensure high reliability.
Watch-dog design of DSP (Digital Signal Processor) increases reliability.
Cold-start capability provides temporary battery power when the utility power is out.
Fan failure detection alerts users to failed fans.
Hot swappable batteries ensure continuous operation even when batteries are being replaced.
Optional external battery pack for easy scaling of longer backup time.
Operation temperature tolerance up to 50°C ensures critical loads' continuity
High output power factor 0.9 provides more real power to critical loads.
Green & Low TCO
High input power factor (pf > 0.99) and low harmonic distortion (iTHD < 5%) save upstream investment.
Up to 94% AC-AC efficiency and 97% efficiency in ECO mode result in marked energy cost savings.
Wide input voltage range reduces the chance of using the battery and extends battery life.
Intelligent battery management sustains battery life and performance.
Fan speed control by load level maximizes efficiency and reduces audible noise.
Flexibility
Load segment control allows less-critical loads to be disconnected during blackouts and saves battery runtime for important loads.
Convertible rack and tower configuration in 2U size cabinet.
Excellent local communications through rotatable LCD display.
Intelligent management software connectivity via RS232 or USB port.
TECHNICAL SPECIFICATIONS
Model
RT-1K / RT-2K / RT-3K
Power Rating
[RT-1K]: 1kVA / 0.9kW
[RT-2K]: 2kVA/ 1.8kW
[RT-3K]: 3kVA/ 2.7kW
Input
Nominal Voltage
200*/208*/220/230/240 Vac
Voltage range
175 ~ 280 Vac (full load)
120 ~ 175 Vac (70 ~ 100% load)
Frequency
40 ~ 70 Hz
Power Factor
> 0.99 (full load)
Current Harmonic Distortion
< 5%
Output
Power Factor
0.9
Voltage
200*/208*/220/230/240 Vac
Voltage Regulation
± 1% (linear load)
Frequency
50/60 Hz ± 0.05 Hz
Voltage Harmonic Distortion
< 2% (linear load)
Overload Capability
< 105%: Continuous
105% ~ 125%: 1 minute
125% ~ 150%: 15 seconds
Receptacle
[RT-1K]: IEC C13 x 6
[RT-2K/3K]: IEC C13 x 6, IEC C19 x 1
Efficiency
AC-AC
[RT-1K]: 90%
[RT-2K/3K]: Up to 94%
ECO Mode
[RT-1K]: 96%
[RT-2K/3K]: Up to 97%
Battery
Battery Voltage
[RT-1K]: 24 Vdc
[RT-2K]: 48 Vdc
[RT-3K]: 72 Vdc
Typical Backup Time**
[RT-1K]: 6.5 minutes
[RT-2K/3K]: 7 minutes
Charge Current
[RT-1K]: 1.5A
[RT-2K/3K]: 2A
Recharge Time
3 hours to 90%
Audible Noise
[RT-1K]: < 40 dBA
[RT-2K]: < 43 dBA
[RT-3K]: < 46 dBA
Display
LCD display and LED indicators
Display
LCD display and LED indicators
Communication Interfaces
SMART Slot x 1, RS-232 Port x 1, USB Port x 1, REPO x 1
Conformance
EN 62040-1, CE, TISI, RCM, EAC
Dimensions (W x D x H)
UPS
[RT-1K]: 440 x 335 x 89 mm
[RT-2K]: 440 x 432 x 89 mm
[RT-3K]: 440 x 610 x 89 mm
External Battery Pack
[RT-1K]: 440 x 335 x 89 mm
[RT-2K]: 440 x 432 x 89 mm
[RT-3K]: 440 x 610 x 89 mm
Weight
UPS
[RT-1K]: 12 kg
[RT-2K]: 18 kg
[RT-3K]: 28 kg
External Battery Pack
[RT-1K]: 15 kg
[RT-2K]: 27 kg
[RT-3K]: 44 kg
Environment
Operating Temperature
0 ~ 50°C***
Relative Humidity
5% ~ 95% (non-condensing)